Permit Information
Permit NumberFIR13-00576
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 10483 W OVERLAND RD
Project NameAUTO ZONE
Customer Number 
ePlanReviewYes
Description
The fire sprinkler scope of work consists of attaching to an existing riser and supplying a new 3” tree system with 2” branch lines. A new 4” backflow preventer will be installed with a wall PIV.

AUTOZONE - STORE #6221) This building is fully fire sprinklered. To construct interior improvement within an existing 6,817 square foot shell space for a retail sales tenant. The building shell was constructed under permit BLD13-00979 as an addition to an existing building. The addition replaced a portion of the building that had been demolished. The entire building has a floor area of about 15,250 square feet. Work is to include interior nonbearing walls, 2 restrooms accessible to the disabled, display shelving, service counters, and interior finishes. Except for the restrooms, the ceiling will be open to the structure above. A separate permit is required for racks over 8 feet tall. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/13/201312/16/201312/16/2013APASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in11/29/201311/29/201311/29/2013PPART
DetailsForrest France
C/N items finished. Remainder of overhead rough-in passed inspection including added heads at entry vestibule, branch line restraints, seismic bracing.
INSP-Sprinkler Rough-in/Hydro11/27/201311/29/201311/29/2013APART
DetailsForrest France
Overhead hydrostatic testing completed satisfactory.
INSP-Sprinkler Rough-in11/12/201311/12/201311/12/2013PPART
DetailsTroy Cobbley
Re-submitt plans showing the arm-overs on the 2" overhead lines which could affect hydraulic calculations as being more demanding than the existing remote area.. Provide branchline restraints. Provide E.Q. bracing as discussed in the riser room. Provide upright sprinkler head in the entry canopy as discussed. Sprinkler piping in the restrooms is ok to cover and the general installation of the overhead lines is passed.
INSP-Conference11/7/201311/8/201311/8/2013ADONE
DetailsTroy Cobbley
Construction at front entry has changed to combustible. I agreed that a single upright head and as-builts showing this addition would suffice. I noted that four way bracing will be required at the top of the main piping at the risers above the restrooms.