Permit Information
Permit NumberFIR13-00670
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 800 W MAIN ST Unit: 200
Project NameOn The Fly Deli
Customer Number 
ePlanReviewYes
Description
The fire sprinkler scope of work consists of adding, plugging and relocating sprinklers to accommodate new wall and ceiling configuration.

The fire sprinkler system is used for high-rise. Permit to create a 1,749 square foot restaurant tenant space on the second story of a new high-rise building. Work is to include interior nonbearing walls, bar stool counter eating, tables, chairs, a walk-in cooler, kitchen equipment, suspended acoustical ceilings, gypsum board soffits and interior finishes. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. **AJS**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/19/20143/20/20143/20/2014APASS
DetailsForrest France
Final walkthrough completed. Fire sprinkler permit finaled.
INSP-Sprinkler Rough-in3/17/20143/17/20143/17/2014PPART
DetailsForrest France
Rough-in passed
INSP-Sprinkler Rough-in3/11/20143/12/20143/12/2014APART
DetailsForrest France
Overhead rough-in passed. Okay for cover at the grid and sheetrock ceilings. Adjustments to upright coverage due to ductwork obstructions approved.