Permit Information
Permit NumberFIR13-00712
StatusFinaled
Name CURTIS FIRE SPRINKLER SERVICE INC
Site Address 5959 N DISCOVERY PL
Project NameYMCA
Customer Number 
ePlanReviewYes
Description
Quick Permit Add, plug and relocate sprinklers to accommodate new wall and ceiling configuration.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/18/20147/18/20147/18/2014PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in4/7/20144/7/20144/7/2014PPART
DetailsForrest France
Okay to cover overhead work at the Tri-classroom and the monitor room as marked and dated on stamped plans.
INSP-Sprinkler Rough-in1/9/20141/10/20141/10/2014APASS
DetailsTroy Cobbley
Pendant head locations in relation to the duct work have been modified and are acceptable. Piping can be covered.
INSP-Sprinkler Rough-in1/8/20141/9/20141/9/2014APART
DetailsTroy Cobbley
Piping installation passed but round duct work installed below the ceiling is causing obstructions. Don and I went over the "three times rule" in NFPA 13. He is going to modify the installation.