INSP-Final Inspection | 4/8/2014 | 4/9/2014 | 4/9/2014 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Sprinkler Rough-in/Hydro | 3/26/2014 | 3/27/2014 | 3/27/2014 | A | FAIL |
Troy Cobbley
|
|
|
Need to provide a Knox Box as per the approved plans and discussion. Need to make the monitoring account "live".
|
INSP-Sprinkler Rough-in/Hydro | 3/7/2014 | 3/13/2014 | 3/13/2014 | A | FAIL |
Troy Cobbley
|
|
|
No city approved plans on site, if shop drawings match city approved resumittal are required showing the changes. Smoke detectors are too close to grills, candellas on strobes are not set correctly, strobes are overspace even if set correctly. FACP has been relocated. Manual pull station has been relocated. No test form provided. No sigal report provided. No test was performed.
|