DOC - Permit Finaled | | | 2/2/2015 | | DONE |
Christina Prado
|
|
|
Status changed by mistake - see inspection notes from 11/12/14
|
INSP-Final Inspection | 11/12/2014 | 11/12/2014 | 11/12/2014 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 11/7/2014 | 11/10/2014 | 11/10/2014 | A | FAIL |
Troy Cobbley
|
|
|
Flow switch tested/passed. Duct smoke detectors still have issues.
|
INSP-Alarm Testing | 11/6/2014 | 11/7/2014 | 11/7/2014 | A | CANC |
Troy Cobbley
|
|
|
Before 11 - Dale Phone #: ###-####
|
INSP-Final Inspection | 11/5/2014 | 11/6/2014 | 11/6/2014 | A | CANC |
Forrest France
|
|
|
Dale-please call with a meet time Phone #: ###-####
|
INSP-Alarm Testing | 7/9/2014 | 7/21/2014 | 7/21/2014 | A | DONE |
Troy Cobbley
|
|
|
The existing duct smoke detectors did not shut down upon detection of smoke. The new duct smoke detectors are not connected to the fire alarm panel. Need the correct orfice in the inspectors test line so that the flow switch can be tested. All other items tested ok.
|