Permit NumberFIR14-00055
StatusFinaled
Name TYCO INTEGRATED SECURITY
Site Address 320 N MILWAUKEE ST
Project NameDarden panel replacement
Customer Number 
ePlanReviewYes
Description
Replace existing damaged FA panel with same panel (new panel is upgraded version of the same panel). No associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
DOC - Permit Finaled  2/2/2015 DONE
DetailsChristina Prado
Status changed by mistake - see inspection notes from 11/12/14
INSP-Final Inspection11/12/201411/12/201411/12/2014PPASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection11/7/201411/10/201411/10/2014AFAIL
DetailsTroy Cobbley
Flow switch tested/passed. Duct smoke detectors still have issues.
INSP-Alarm Testing11/6/201411/7/201411/7/2014ACANC
DetailsTroy Cobbley
Before 11 - Dale Phone #: ###-####
INSP-Final Inspection11/5/201411/6/201411/6/2014ACANC
DetailsForrest France
Dale-please call with a meet time Phone #: ###-####
INSP-Alarm Testing7/9/20147/21/20147/21/2014ADONE
DetailsTroy Cobbley
The existing duct smoke detectors did not shut down upon detection of smoke. The new duct smoke detectors are not connected to the fire alarm panel. Need the correct orfice in the inspectors test line so that the flow switch can be tested. All other items tested ok.