Permit Information
Permit NumberFIR14-00076
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 4321 S KENNEDY ST
Project NameWESTERN AIRCRAFT INFILL BUILD
Customer Number 
ePlanReviewYes
Description
The fire sprinkler scope of work consists of reworking an existing riser. Running a new bulk main across an existing hanger to a new infill section. The new infill section is two stories. The fire floor is a shop area protected as Ordinary Hazard II. The second floor is office and protected as light hazard. There is a new riser on the second floor. Both floors are protected with small tree type layouts.

Western Aircraft - Shop and Office Addition - To construct an 11,465 square foot, two story, pre-engineered metal building shop, storage and office building addition between two existing aircraft hangars. This will create one large building with a three-hour fire wall separating the new addition from the north existing hangar, creating separate buildings for allowable area and allowed nonseparated uses. This building is fully fire sprinklered. The sprinklers are used for area increase. This permit also includes related site improvements. All construction per the approved plans attached comment list. JCM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/6/20146/6/20146/6/2014APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection6/5/20146/5/20146/5/2014PCANC
DetailsTroy Cobbley
Not ready for final due to alarm issues
INSP-Sprinkler Rough-in5/28/20145/28/20145/28/2014PPASS
DetailsTroy Cobbley
Overhead rough-in passed for the 4" wet system from the riser room to the new "infill".
INSP-Sprinkler Rough-in/Hydro5/27/20145/27/20145/27/2014PPASS
DetailsTroy Cobbley
Overhead hydro test of the 4" wet system passed
INSP-Sprinkler Rough-in5/19/20145/19/20145/19/2014PPASS
DetailsTroy Cobbley
Piping above the lay in ceilings on the first and second floors is ok to cover
INSP-Sprinkler Rough-in/Hydro4/8/20144/8/20144/8/2014PPASS
DetailsTroy Cobbley
First and second floor rough-in and overhead hydro passed for the In-Fill