Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberFIR14-00095
StatusFinaled
Name SENTRY SECURITY SYSTEMS
Site Address 4632 W AERONCA ST
Project NameAviation Specialties Unlimited
Customer Number 
ePlanReviewNo
Description
Sprinkler monitoring with elevator recall and remote annunciator. Associated building permit: Bld13-00906
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/13/20154/13/20154/13/2015PPASS
DetailsKatie Marron
Remainder of fire alarm work completed. Inspection of flow and tamper switch pass. Fire Alarm Bell connection fixed on sight.
INSP-Alarm Testing10/1/201410/1/201410/1/2014PDONE
DetailsTroy Cobbley
Fire alarm complete in the new hanger. 110 power at the elevator and door mag has been repaired.
INSP-Final Inspection9/26/20149/26/20149/26/2014PFAIL
DetailsTroy Cobbley
To complete the fire alarm in the new area I need the 110 power of the elevator monitored and the door mags to release upon general alarm.
INSP-Sprinkler Rough-in/Hydro9/24/20149/25/20149/26/2014PCANC
DetailsTroy Cobbley
Canceled due to time constraints
INSP-Final Inspection9/11/20149/12/20149/12/2014AFAIL
DetailsTroy Cobbley
Items test today included tamper switches for the backflow, hose valve and new hanger riser. Also included were the new hanger flow switch, smoke, pull, phone lines and loss of a/c. Elevator and riser to existing building is not complete. Need breaker lock and breaker identified. Electric alarm bell not installed yet.