Permit Information
Permit NumberFIR14-00127
StatusVoid/No Violation
Name AUDIO ELECTRONICS INC
Site Address 2509 S BROADWAY AVE
Project NameOffice Max FA System Remod
Customer Number 
ePlanReviewYes
Description
The existing system does not have any supervised circuits (IDC or NAC). FACP is to be relocated from above the ceiling, to an accessible space, and the smoke detector will be relocated to above the FACP. The Remote annunciator will be relocated to the front entry. Open air splices will be enclosed.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/28/20149/3/20149/3/2014AFAIL
DetailsTroy Cobbley
NFPA "Testing and Inspeciton" form and "signal test reports not provided. Heights of notification devices have been modified. NAC/Power Supplies have been provided for each of the two notification circuits. Neither one of these items is shown on the plans. Per conversation with plan review notification shall be provided through-out as per NFPA 72. I noted that the north side of the building strobes flash about once every second. The south side strobes flash once every six seconds and the horn tone is "solid tone". It appears that none of the NAC or IDC curcuits are supervised. We tested the smoke detector at the FACP and a manual pull station which registered correctly at the remote annunciator. Plans need to be submitted showing all devices utilized, correct scope of work and actual field conditions/function of the fire alarm system. See NFPA 72; (18.4.2 temporal), (18.5.3.1 strobe flash rate), (10.8.2.3 supervision/trouble signals)