Permit Information
Permit NumberFIR14-00182
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 951 E FRONT ST
Project Name916 Park Apartments
Customer Number 
ePlanReviewYes
Description
Park Apts is a new FA System in a New Building. We are installing a new 4010ES Simplex panel, Remote Annunciator, Horn Strobes on common areaas and mini horn on each apartment units. Elevator control and sprinkler monitoring complete the system. Associated building permit: BLD12-02886.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/14/20151/14/20151/15/2015PPASS
DetailsForrest France
Noted corrections and adjustments verified. Final inspection passed. Fire alarm permit finaled.
INSP-Alarm Testing1/12/20151/13/20151/13/2015ANR
DetailsForrest France
Mag locks at exit doors failed to release upon general alarm condition.
INSP-Sprinkler Rough-in/Hydro1/12/20151/13/20151/12/2015ACANC
DetailsForrest France
As late as possible Phone #: 2089411846 >> Inspection requested via mobile web by Brian Anderson Inspection cancelled via mobile web on Monday, January 12, 2015.
INSP-Final Inspection1/9/20151/9/20151/12/2015PCANC
DetailsForrest France
As early as possible Phone #: 2089414511 >> Inspection requested via mobile web by Nathan Price Inspection cancelled via mobile web on Monday, January 12, 2015.
INSP-Final Inspection1/9/20151/12/20151/12/2015AFAIL
DetailsTroy Cobbley
For todays inspection I verified audible/visuals for the first and fourth floors including live/work units. I also verified in-duct dectors on the first floor. Only two fire smoke dampers were accessible. All of the others require better access. Elevators and other items were not ready.
INSP-Alarm Testing1/5/20151/7/20151/8/2015PFAIL
DetailsForrest France
Plan modification will be necessary due to numerous changes to the original design and approved plans including; approx 25 new ID detectors, mag locks at three sets of doors, added smoke and heat detection at the elevator hoistway, relocated sprinkler risers, new ADA rooms and notification appliances, revised matrix, etc. Need to provide notification at the gym restroom, post signage at the FACP room door. Elevator is not in service to complete recall and shunt tests.