INSP-Final Inspection | 9/11/2014 | 9/12/2014 | 9/12/2014 | A | PASS |
Troy Cobbley
|
|
|
Plan modification approved. Permit finaled
|
INSP-Final Inspection | 8/26/2014 | 8/27/2014 | 8/27/2014 | A | FAIL |
Troy Cobbley
|
|
|
No additional notification devices are needed per Lee but the as-builts need to be approved prior to a final sign off. Any corrections noted on the newly approved plans will need to be implimented.
|
INSP-Final Inspection | 5/8/2014 | 5/13/2014 | 5/13/2014 | A | FAIL |
Troy Cobbley
|
|
|
All alarm audible devices must sync. NFPA 7218.4.2.4, All visual devices must sync NFPA 7218.5.5.4.2, All audible alarm devices shall use "temporal tone" NFPA 7218.4.2.1, All areas/notification shall activate upon alarm IFC907.6, Provide fire alarm notification devices through out all required areas as per IFC 907 and installed per NFPA 72. If wanted provide upgrade agreement, as discussed, to Scott Arellano for review.
|