INSP-Final Inspection | 8/15/2014 | 8/18/2014 | 8/18/2014 | P | PASS |
Forrest France
|
|
|
C/N items completed. Remainder of fire alarm work passed functional testing and inspection. Permit finaled.
|
INSP-Final Inspection | 8/12/2014 | 8/15/2014 | 8/15/2014 | A | PART |
Forrest France
|
|
|
Items noted include; remove remainder of MP stations per the scope of work, new tamper switch supervision, remove remainder of old horns, clear obstructions at duct detector vent tubes, provide EOL testing for notification circuts on battery power. Duct detectors for unit shutdown tested okay.
|