Permit Information
Permit NumberFIR14-00246
StatusFinaled
Name MOUNTAIN ALARM
Site Address 250 W BOBWHITE CT
Project NameGreystone Bldg. FACP replace
Customer Number 
ePlanReviewNo
Description
Replace existing fire alarm panel that is failing. Existing field devices are to remain. Install a new AES wireless communicator. There is no assciated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/20/201410/21/201410/21/2014APASS
DetailsForrest France
Completed functional testing of notification appliances, verified monitoring, riser supervision, trouble condition. Documents cabinet posted. Fire alarm permit finaled.
INSP-Final Inspection10/8/201410/9/201410/9/2014PPART
DetailsForrest France
Verified plan modification, netcon rating, additions and relocations of both notification and initiation devices per notes. Final pending functional testing of a/v's, need access to riser room, post documents cabinet, coordinate audible testing with building occupants advance of inspection as discussed.
INSP-Conference9/10/20149/10/20149/10/2014PDONE
DetailsForrest France
INSP-Final Inspection8/26/20148/27/20148/27/2014AFAIL
DetailsForrest France
Items noted include; netcon of 7 at the time of inspection, need to provide addtional notification at some areas on the 3rd and 2nd floors, relocate MP at the 3rd floor NE exit, verify sync between EST and system sensor brand notification devices in suite 275. Provide a plan modification for resubmittal to include all field changes such as added power supplies, added SD, matrix change for deletion of elevator recall, correct zones at panel, added notification devices throughout all three floor levels, floorplan changes, etc. Approved plan set to match field install.