Permit Information
Permit NumberFIR14-00306
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 4321 S KENNEDY ST
Project NameWestern Aircraft In-Fill & Han
Customer Number 
ePlanReviewYes
Description
The scope of this work is to completely migrate the existing system in the Western Aircraft office, hanger1 infill and hanger two to a new addressable platform fire alarm system. Additionally this quote is to implement a new code minimum system in the new infill TI area and to implement a new high expansion foam detection and releasing system for the existing hanger 2. The existing system will be demoed and discarded.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/1/201411/3/201411/3/2014APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection10/30/201410/30/201410/30/2014PPART
DetailsTroy Cobbley
Tested the protecto wire activation of the deluge system in the new hanger. Functioned as required.
INSP-Final Inspection9/18/20149/19/20149/19/2014APART
DetailsTroy Cobbley
See the city as-builts for devices marked "ok" that were tested today. As-builts show duplicate addresses in the elevator machine room that will need to be corrected. One smoke detector in the elevator machine room did not recall the elevator.
INSP-Final Inspection6/5/20146/6/20146/6/2014APART
DetailsTroy Cobbley
A temporary is being given as the work in the riser room and the in-fill is completed except for the elevator recall and related components. All other work outside of the in-fill has not been inspected/tested yet. Resubmittals are required to show the additional flow switch, tamper switch and instead of phone lines a DSC communicator has been installed. No final sign off untill plans are re-approved.
INSP-Final Inspection6/5/20146/5/20146/5/2014PCANC
DetailsTroy Cobbley
Not ready for inspection due to dialer issue