INSP-Final Inspection | 11/1/2014 | 11/3/2014 | 11/3/2014 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 10/30/2014 | 10/30/2014 | 10/30/2014 | P | PART |
Troy Cobbley
|
|
|
Tested the protecto wire activation of the deluge system in the new hanger. Functioned as required.
|
INSP-Final Inspection | 9/18/2014 | 9/19/2014 | 9/19/2014 | A | PART |
Troy Cobbley
|
|
|
See the city as-builts for devices marked "ok" that were tested today. As-builts show duplicate addresses in the elevator machine room that will need to be corrected. One smoke detector in the elevator machine room did not recall the elevator.
|
INSP-Final Inspection | 6/5/2014 | 6/6/2014 | 6/6/2014 | A | PART |
Troy Cobbley
|
|
|
A temporary is being given as the work in the riser room and the in-fill is completed except for the elevator recall and related components. All other work outside of the in-fill has not been inspected/tested yet. Resubmittals are required to show the additional flow switch, tamper switch and instead of phone lines a DSC communicator has been installed. No final sign off untill plans are re-approved.
|
INSP-Final Inspection | 6/5/2014 | 6/5/2014 | 6/5/2014 | P | CANC |
Troy Cobbley
|
|
|
Not ready for inspection due to dialer issue
|