Permit Information
Permit NumberFIR14-00325
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 2400 S MAPLE GROVE RD
Project NameInvolta Data Center
Customer NumberUDG ONLY
ePlanReviewYes
Description
The fire sprinkler scope of work consists of adding a double interlock preaction system, a supply for a future double interlock preaction system and a wet system. The preaction system is a double tree supplied through 6” underground and a 6” header. The tree is a grid type layout.

The underground was installed under permit FIR14-00325

(INVOLTA DATA CENTER) This submittal is for tenant improvement construction permit. Civil and Structural Footing/Foundation/Steel packages were previously submitted and approved under separate permits.

Project is for a new, single-story, 31,460 square foot data center and office tenant, with future 15,400 square foot Phase 2 (to be permitted separately at future date). This building will provide secure data storage for multiple customers. The facility will be staffed 24 hours a day, 7 days a week. Work to include...

Contractor’s Note:
The building permit has not been issued at this time. The building department may determine that changes are required to the building plans in order to meet code. The changes may affect the sprinkler system. The sprinkler contractor will be obligated to make all necessary changes that may be required. Therefore, if the sprinkler contractor chooses to proceed without an issued building permit, they will do so on their own cognizance. This note does not constitute an early start agreement.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/10/201410/10/201410/10/2014PPASS
DetailsTroy Cobbley
permit finaled
INSP-Supply line flush10/10/201410/10/201410/10/2014PPASS
DetailsTroy Cobbley
UG flush passed
INSP-Sprinkler Rough-in9/3/20149/4/20149/4/2014PCANC
DetailsTroy Cobbley
Wrong permit number called in. Rick Phone #: ###-####
INSP-Sprinkler Rough-in/Hydro8/18/20148/19/20148/19/2014APART
DetailsForrest France
UG fire supply line passed hydrostatic testing.
INSP-Sprinkler Rough-in/Hydro7/23/20147/24/20147/24/2014ACANC
DetailsTroy Cobbley
Troy-Underground Hydro Phone #: ###-####
INSP-Final Inspection7/17/20147/18/20147/18/2014APASS
DetailsTroy Cobbley
The remaining underground piping is ok to cover.
INSP-Sprinkler Rough-in7/17/20147/17/20147/17/2014PPASS
DetailsTroy Cobbley
The remaining underground is ok for cover except for the thrust blocks which will be verified tomorrow.
INSP-Sprinkler Rough-in7/15/20147/16/20147/16/2014PPASS
DetailsTroy Cobbley
See the city approved underground drawings for location where the underground supply line can be buried.