INSP-Final Inspection | 6/12/2015 | 6/12/2015 | 6/12/2015 | A | PASS |
Thomas Walsh
|
|
|
Final inspection of Wings A & B buildings, including elevator recall functions, and SFDs - PASSED
|
INSP-Alarm Testing | 6/8/2015 | 6/8/2015 | 6/8/2015 | P | PART |
Thomas Walsh
|
|
|
Inspection/ test of fire alarm system for the permit coverage area, including manual pulls, smoke detection, waterflows, tamper supervisories, and audibility/visual device testing. All addresses appeared to be accurate. NOTE: No FSDs or elevator functions tested this visit.
|
INSP-Alarm Testing | 6/8/2015 | 6/15/2015 | 6/8/2015 | P | CANC |
Thomas Walsh
|
|
|
Call prior to going Phone #: 2089411846 >> Inspection requested via mobile web by Brian A Inspection cancelled via mobile web on Monday, June 08, 2015.
|
INSP-Sprinkler Rough-in/Hydro | 6/8/2015 | 6/15/2015 | 6/8/2015 | P | CANC |
Thomas Walsh
|
|
|
Call prior to going Phone #: 2089411846 >> Inspection requested via mobile web by Brian A Inspection cancelled via mobile web on Monday, June 08, 2015.
|
INSP-Conference | 1/22/2015 | 1/23/2015 | 1/23/2015 | P | DONE |
Forrest France
|
|
|
On site visit with contractor regarding SA locations at living units- discussed min. distances from HVAC registers, ceiling fans, bathroom doors, cooking appliances, walls, etc. Also noted missing visual notification at ADA unit guest bathrooms and obstructed coverage at units provided with a divided vanity adjacent to the bedroom.
|