Permit Information
Permit NumberFIR14-00353
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 6623 W COLEHAVEN DR
Project NameAberdeen 4Plex:#6623 Colehaven
Customer Number 
ePlanReviewYes
Description
The fire sprinkler scope of work consists of protecting a 4 unit apartment building. Cpvc pipe and extended throw residential sprinklers are being utilized.

L4B2 - 6623 Colehaven - (Bldg 1) To construct a new 3,960 sq. ft., two story, Four unit, apartment building. Each unit has two bedrooms, and two bathrooms. The 1st story units are required to be Type 'B' units. All units share a common path of egress into and through a 1-hour rated exit corridor with 20-minute fire-resistive, listed, labeled, self-closing door assemblies from the dwelling units into the corridor. All construction per the approved plans, attached plan review report, and all other reviewing agencies approvals. One-hour fire-partitions and one hour horizontal assemblies are required between dwelling units. This building is required to be fire sprinklered. The fire sprinkler system shall be per NFPA 13R as regulated by the fire department. DRH13-00276 & CUP13-00017 Per Planning and Zoning. **SRZ**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/4/20148/6/20148/6/2014APASS
Details
System tested and pass
INSP-Supply line flush7/22/20147/23/20147/23/2014APASS
DetailsTroy Cobbley
Underground supply line flush passed
INSP-Sprinkler Rough-in6/25/20146/25/20146/27/2014PPART
DetailsForrest France
Okay to cover overhead fire sprinkler work. Tenting 2nd floor okayed. Need to provide intermediate temp heads at the furnace closets.
INSP-Sprinkler Rough-in/Hydro6/24/20146/25/20146/25/2014APART
DetailsForrest France
OH hydrostatic test completed satisfactory. Tenting needs adjusted at the second floor south apt.