INSP-Final Inspection | 10/14/2015 | 10/14/2015 | 10/15/2015 | P | PASS |
Thomas Walsh
|
|
|
Final Inspection passed. All previous discrepancies corrected.
|
INSP-Final Inspection | 6/25/2015 | 6/25/2015 | 6/25/2015 | P | PASS |
Thomas Walsh
|
|
|
Final inspection for wings A-D parking garage, including fire pump room. PASSED
|
INSP-Sprinkler Rough-in/Hydro | 6/12/2015 | 6/12/2015 | 6/12/2015 | P | PASS |
Thomas Walsh
|
|
|
Final Inspection of under ground parking for wings A, B C, including the fire pump room. All fire alarm interface, such as waterflow and tampers were tested with the fire alarm system. Riser placards were applied. No discrepancies remained for this portion of the overall system.
|
INSP-Final Inspection | 6/10/2015 | 6/11/2015 | 6/11/2015 | A | PART |
Thomas Walsh
|
|
|
Final inspection of U/G parking garage wet system. NOTE: Fire caulking needed at stair # 3 pipe penetration. Also need to inspect fire pump room, as this room is under this permit.
|
INSP-Sprinkler Rough-in/Hydro | 6/9/2015 | 6/10/2015 | 6/10/2015 | A | PASS |
Thomas Walsh
|
|
|
Boise PDS witnessed fire pump test (Tim Frost and Tom Walsh), incuding pump flow tests to record proper flows and pressures at various stages of the pump operations, also phase reversal, and fire alarm system interface. All tested OK - final fire pump signoff will require room upgrades (1 hour room), including fire rated door installed, emergency lighting, wall penetrations fire stopped, etc. Also all weather sign on exterior of pump room door.
|
INSP-Final Inspection | 6/5/2015 | 6/8/2015 | 6/8/2015 | P | PART |
Thomas Walsh
|
|
|
Inspection of fire alarm system interface, including water flows of system risers, tamper devices, control valves, etc. Waterflows came in at approx. 30-40 seconds.All pump room tampers tested OK. All device addresses appeared accurate.
|
INSP-Sprinkler Rough-in/Hydro | 4/21/2015 | 4/21/2015 | 4/23/2015 | P | CANC |
Katie Marron
|
|
|
Cancelled overbooked, rescheduled for later date.
|