Permit NumberFIR14-00373
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 800 W MAIN ST Unit: 1400
Project NameDeloitte TI 14th Floor
Customer Number 
ePlanReviewYes
Description
The fire sprinkler scope of work consists of adding, plugging and relocating sprinklers to accommodate new wall and ceiling configuration.

Fire sprinklers used for high-rise. To create a 6,605 square foot office tenant space on the 18,300 square foot 14th story of a new high-rise building. Work is to include interior nonbearing walls, interior doors and sidelights, card readers, suspended acoustical ceilings, millwork, and finishes. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/8/20148/8/20148/8/2014PPASS
DetailsForrest France
Fire sprinkler permit finaled.
INSP-Sprinkler Rough-in7/30/20147/31/20147/31/2014PPART
DetailsForrest France
Noted two missing hangers at armovers, one pendent head in need of alignment, obstruction at one head due to an exit sign. Remainder of overhead work approved for cover. Painted escutcheon at the west elevator lobby sheetrock ceiling to be replaced.