INSP-Final Inspection | 11/4/2014 | 11/4/2014 | 11/4/2014 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Alarm Testing | 8/27/2014 | 8/28/2014 | 8/28/2014 | A | CANC |
Troy Cobbley
|
|
|
Canceled per Nathan Price and my discussion.
|
INSP-Final Inspection | 8/26/2014 | 8/27/2014 | 8/27/2014 | A | FAIL |
Troy Cobbley
|
|
|
Not ready for a final yet but we did verify that the flow switch and single tamper switch to the three story office was functional. We stopped the inspection after this due to installation (addresses/physical location) did not match the approved plans. As-bults are needed. I noted that not all manual pull stations meet height requirements of NFPA 72 and will need to be corrected. No testing of the suppression system was performed. FACP panel/batteries/power supply was verified. Need breaker labeling and lockout.
|