INSP-Final Inspection | 3/27/2015 | 3/30/2015 | 3/30/2015 | P | PASS |
Forrest France
|
|
|
Final inspection passed. Outside waterflow bell repaired.
|
INSP-Final Inspection | 3/26/2015 | 3/27/2015 | 3/27/2015 | A | NH |
Forrest France
|
|
|
No access to complete inspection
|
INSP-Sprinkler Rough-in/Hydro | 3/23/2015 | 3/24/2015 | 3/24/2015 | A | PART |
Forrest France
|
|
|
Completed satisfactory hydrostatic test of the new dry system piping.
|
INSP-Final Inspection | 3/23/2015 | 3/23/2015 | 3/23/2015 | P | PART |
Forrest France
|
|
|
Final Inspection above ground please call Leroy 30 min prior ###-#### Phone #: ###-#### Inspection requested via web by Jacci Hunt
|
INSP-Final Inspection | 2/3/2015 | 2/5/2015 | 2/5/2015 | P | PART |
Forrest France
|
|
|
Concluded satisfactory pneumatic test of the dry system with no pressure loss at the guage.
|
INSP-Sprinkler Rough-in | 2/3/2015 | 2/4/2015 | 2/4/2015 | P | PART |
Forrest France
|
|
|
Begin 24 hr air test of the new dry system at 43psig @ 3:15PM.
|
INSP-Sprinkler Rough-in | 1/19/2015 | 1/21/2015 | 1/21/2015 | P | CANC |
Forrest France
|
|
|
Please schedule 24 hour air test. Must be done after 3:30 pm Pls call Leroy 30 mins prior Phone #: ###-#### >> Inspection requested via web by Jacci Hunt Inspection cancelled from web by: Jacci Hunt
|
INSP-Sprinkler Rough-in | 1/19/2015 | 1/20/2015 | 1/19/2015 | P | CANC |
Forrest France
|
|
|
Please schedule 24 hour air test. Must be done after 3:30 pm Please call Leroy 30 mins prior Phone #: ###-#### >> Inspection requested via web by Jacci Hunt Inspection cancelled from web by: Jacci Hunt
|
INSP-Sprinkler Rough-in/Hydro | 1/13/2015 | 1/14/2015 | 1/14/2015 | P | FAIL |
Forrest France
|
|
|
24 hr air test failed due to an 8 psi loss at the guage-
|
INSP-Sprinkler Rough-in | 1/12/2015 | 1/13/2015 | 1/13/2015 | P | PART |
Forrest France
|
|
|
Begin 24 hr air test of the new dry system -2:00PM@ 43 psig.
|
INSP-Sprinkler Rough-in | 1/8/2015 | 1/9/2015 | 1/12/2015 | P | PART |
Forrest France
|
|
|
OH rough-in of the new dry system completed satisfactory. Dry pendents at the library are not yet installed.
|