Permit NumberFIR14-00437
StatusFinaled
Name PHOENIX FIRE PROTECTION
Site Address 1725 E WARM SPRINGS AVE
Project NameAdams Elementary
Customer Number 
ePlanReviewYes
Description
The fire sprinkler scope of work consists of protecting an existing attic with a new dry system. The system utilizes special application attic sprinklers.

There is no associated building permit for this project.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/27/20153/30/20153/30/2015PPASS
DetailsForrest France
Final inspection passed. Outside waterflow bell repaired.
INSP-Final Inspection3/26/20153/27/20153/27/2015ANH
DetailsForrest France
No access to complete inspection
INSP-Sprinkler Rough-in/Hydro3/23/20153/24/20153/24/2015APART
DetailsForrest France
Completed satisfactory hydrostatic test of the new dry system piping.
INSP-Final Inspection3/23/20153/23/20153/23/2015PPART
DetailsForrest France
Final Inspection above ground
please call Leroy 30 min prior ###-#### Phone #: ###-#### Inspection requested via web by Jacci Hunt
INSP-Final Inspection2/3/20152/5/20152/5/2015PPART
DetailsForrest France
Concluded satisfactory pneumatic test of the dry system with no pressure loss at the guage.
INSP-Sprinkler Rough-in2/3/20152/4/20152/4/2015PPART
DetailsForrest France
Begin 24 hr air test of the new dry system at 43psig @ 3:15PM.
INSP-Sprinkler Rough-in1/19/20151/21/20151/21/2015PCANC
DetailsForrest France
Please schedule 24 hour air test. Must be done after 3:30 pm
Pls call Leroy 30 mins prior Phone #: ###-#### >> Inspection requested via web by Jacci Hunt Inspection cancelled from web by: Jacci Hunt
INSP-Sprinkler Rough-in1/19/20151/20/20151/19/2015PCANC
DetailsForrest France
Please schedule 24 hour air test. Must be done after 3:30 pm
Please call Leroy 30 mins prior Phone #: ###-#### >> Inspection requested via web by Jacci Hunt Inspection cancelled from web by: Jacci Hunt
INSP-Sprinkler Rough-in/Hydro1/13/20151/14/20151/14/2015PFAIL
DetailsForrest France
24 hr air test failed due to an 8 psi loss at the guage-
INSP-Sprinkler Rough-in1/12/20151/13/20151/13/2015PPART
DetailsForrest France
Begin 24 hr air test of the new dry system -2:00PM@ 43 psig.
INSP-Sprinkler Rough-in1/8/20151/9/20151/12/2015PPART
DetailsForrest France
OH rough-in of the new dry system completed satisfactory. Dry pendents at the library are not yet installed.