INSP-Final Inspection | 8/5/2014 | 8/6/2014 | 8/6/2014 | A | PASS |
Forrest France
|
|
|
Verified previous correction items. Functional testing passed. Fire alarm permit finaled.
|
INSP-Alarm Testing | 7/24/2014 | 7/25/2014 | 7/25/2014 | P | DONE |
Troy Cobbley
|
|
|
Second floor fire alarm complete. Plan modifications will need to be approved showing the location of the new NAC panel, smoke detector, change in trigger point and the change of notification devices.
|
INSP-Final Inspection | 7/21/2014 | 7/22/2014 | 7/22/2014 | A | FAIL |
Troy Cobbley
|
|
|
Todays testing was for the second floor only. All devices function correctly except a new NAC panel has been installed on the second floor and the new audio devices do not sync with the existing audio devices. Per myself and Lee's conversation with the contractors, plan modifications are required prior to a final sign off for the entire project but the sync issue needs to be addressed prior to second floor occupancy. All fire alarm devices were to function correctly as per phone/email conversation with the fire alarm contractor dated 7/7/2014.
|