Permit Information
Permit NumberFIR14-00464
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 699 N MITCHELL ST
Project NameHORIZON PARK APTS.
Customer Number 
ePlanReviewYes
Description
The fire sprinkler scope of work consists of 8-unit apartment building. CPVC pipe and extended throw residential sprinklers are being utilized.

Horizon Park - Eight Unit Apartment Building (First floor apt. #s 101,102,103,104, Second floor #s 201,202,203,204). Permit for the construction of a new 2 story, 8 unit apartment building per the approved plans. The building has 4,800 sq. ft. per story including common areas with 4 apartments on each story. This building is fully fire sprinklered per residential occupancy requirements and shall comply with NFPA13 as regulated by the Fire Department. CDM

Contractor’s Note:
The building permit has not been issued at this time. The building department may determine that changes are required to the building plans in order to meet code. The changes may affect the sprinkler system. The sprinkler contractor will be obligated to make all necessary changes that may be required. Therefore, if the sprinkler contractor chooses to proceed without an issued building permit, they will do so on their own cognizance. This note does not constitute an early start agreement.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/29/20156/30/20156/30/2015APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection6/29/20156/29/20156/29/2015PFAIL
DetailsTroy Cobbley
Need signage on risers, need time on flow switches changed, need to verify bell functions. I need to walk through and verify heads.
INSP-Sprinkler Rough-in10/15/201410/16/201410/16/2014APASS
DetailsTroy Cobbley
Tenting inspection passed. Piping can be covered.
INSP-Sprinkler Rough-in10/14/201410/15/201410/15/2014PPASS
DetailsTroy Cobbley
Sprinkler rough-in passed. Tim is ok with the changes as per email. Piping can not be covered until a tenting inspection.
INSP-Sprinkler Rough-in/Hydro10/8/201410/9/201410/9/2014APART
DetailsTroy Cobbley
Overhead hydro tests passed. Piping, as installed/rough-in passed. But routeing and fitting counts have changed and per the review notes any modifications will require resubmittals. So prior to an approval for cover being given I need plan modifications and a tenting inspection.
INSP-Supply line flush10/7/201410/8/201410/8/2014APASS
DetailsTroy Cobbley
Underground flush passed
INSP-Sprinkler Rough-in8/27/20148/28/20148/28/2014APASS
DetailsTroy Cobbley
The underground supply piping is ok to cover.
INSP-Sprinkler Rough-in8/27/20148/27/20148/27/2014PCANC
DetailsTroy Cobbley
Not ready for an inspection yet due to no piping in the trench.