Description
Provide a code compliant fire alarm system to a new two story medical/office building. Associated with building permit BLD13-03291
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/5/20151/5/20151/5/2015PPASS
DetailsForrest France
Fire alarm permit finaled.
INSP-Alarm Testing1/5/20151/5/20151/5/2015PPASS
DetailsForrest France
Verified remainder of correction items. Inspection and functional testing completed satisfactory.
INSP-Final Inspection12/30/20141/2/20151/2/2015ANR
DetailsForrest France
Today's inspection rescheduled per contractor request. Initial site inspection completed 12/31- noted correction items included; relocate SD at elevator lobby second floor, provide missing strobe or revise cd setting at the first floor hallway SE end, PIV tamper switch adjustment, first floor flow switch adjustment, drawings to reflect field changes of deleted SD at patient rooms, deleted SD and HD at the elevator hoistway and deleted duct detectors. Monitoring and account information set up finished while on site 12/31 PM.