INSP-Final Inspection | 2/17/2015 | 2/17/2015 | 2/18/2015 | P | PASS |
Tim Frost
|
|
|
Verified previous correction items. Final inspection and functional testing passed. Permit finaled.
|
INSP-Final Inspection | 10/16/2014 | 10/22/2014 | 10/22/2014 | P | FAIL |
Forrest France
|
|
|
C/N items include; provide tamper switch at the PIV, repair outside waterflow bell, provide knox box, relocate SD used for door release service at the 2nd floor level, basement level lobby SD did not initiate elevator recall, fire hat flash is not functional. Refer to plan review notes items #3,8,12,13,23 for details.
|
INSP-Final Inspection | 10/2/2014 | 10/3/2014 | 10/3/2014 | P | DEFR |
Forrest France
|
|
|
|