INSP-Final Inspection | 8/8/2014 | 8/8/2014 | 8/8/2014 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Alarm Testing | 8/5/2014 | 8/6/2014 | 8/6/2014 | A | PART |
Forrest France
|
|
|
Functional testing completed acceptable. Final pending location of smoke detectors at the north and south corridors 154 and 162 east side of the new fire doors. Relocate away from HVAC diffusers or delete and meet NFPA 72 17.7.5.6.1.
|
INSP-Final Inspection | 8/4/2014 | 8/5/2014 | 8/5/2014 | A | FAIL |
Troy Cobbley
|
|
|
Fire alarm panel is in trouble. Electrician wanted to work on it. No testing performed.
|
INSP-Final Inspection | 8/4/2014 | 8/4/2014 | 8/4/2014 | A | CANC |
Troy Cobbley
|
|
|
Cancel per Brian and I's discussion. Call for access Phone #: 2089411846 >> Inspection requested via mobile web by Brian A
|