Permit NumberFIR14-00518
StatusFinaled
Name TASKER ELECTRICAL CONSTRUCTION INC
Site Address 8455 W WESTPARK ST
Project Name8455 Westpark East Warehouse
Customer Number 
ePlanReviewNo
Description
This parcel is being separated into two parcels, thus requiring separate fire alarm systems. Existing panel is to be removed and two new systems will be installed under separate permits. (FIR14-00517 and FIR14-00518) Fire alarm panel replacement is for sprinkler monitoring of Vanilla Finish warehouse. Associated with building permit BLD14-02274.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/14/20161/15/20161/15/2016APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection1/13/20161/14/20161/14/2016PFAIL
DetailsTroy Cobbley
Need the as-built drawings as discussed and then the project can be finaled.
INSP-Final Inspection2/5/20152/6/20152/6/2015AFAIL
DetailsTroy Cobbley
Fire alarm testing complete. Need the non-functional hvac units repaired or removed. If repaired I need to finish testing. If removed I need revised drawings.
INSP-Final Inspection1/29/20151/30/20151/30/2015AFAIL
DetailsTroy Cobbley
Need plan modificatios and the hvac unit/shut down addressed.
INSP-Final Inspection1/29/20151/29/20151/29/2015AFAIL
DetailsTroy Cobbley
We were only able to test one duct smoke detector due to not being able to get the remaining hvac units to function. I noted that the smoke detectors for the fire door release do not appear to be installed per NFPA 80 and Chapter 17 of NFPA 72
INSP-Final Inspection1/29/20151/30/20151/29/2015ACANC
DetailsTroy Cobbley
Please notify Greg 30 min. prior to arrival. Thank you! Phone #: ###-#### >> Inspection requested via web by Stacie Tasker Inspection cancelled from web by: Stacie Tasker
INSP-Final Inspection1/27/20151/28/20151/28/2015AFAIL
DetailsTroy Cobbley
Resubmit plans for a "plan modification" for the additional flow switches, tamper switches and the cellular dialer. Provide auto-resetting tamper switches on the existing anti-freeze loop control valves, repair or remove the non-functional hvac units to facilitate the testing of the duct smoke detectors, remove or provide connection to the door mags.
INSP-Final Inspection8/8/20148/8/20148/8/2014PFAIL
DetailsTroy Cobbley
Provide city approved data sheets and as-builts/submittals as discussed. Functional testing of system passed.