INSP-Final Inspection | 7/26/2015 | 7/27/2015 | 7/27/2015 | A | PASS |
Jim Page
|
|
|
Previously noted items corrected, Dry pendant escutcheons on order, will be installed when received, fire sprinkler inspection passed/complete
|
INSP-Final Inspection | 7/23/2015 | 7/24/2015 | 7/24/2015 | A | PART |
Jim Page
|
|
|
Trip test of the dry pipe valve, including the new accelerator - tested OK within 45 seconds. Escutcheons missing on multiple heads in parking area, need to have air maintenance installed on air line supply to dry system, compressor provided regulator not approved for air maintenance.
|
INSP-Final Inspection | 7/20/2015 | 7/20/2015 | 7/20/2015 | P | FAIL |
Thomas Walsh
|
|
|
Trip test of dry pipe valve protecting perking garage. Trip test resulted in 90 seconds to delivery of water to IT. Contractro agreed to install an accelerator to get within 60 seconds timeframe. All other tests, including low-air, tampers, ext. bell, etc., tested OK
|
INSP-Sprinkler Rough-in/Hydro | 7/16/2015 | 7/16/2015 | 7/16/2015 | P | PASS |
Thomas Walsh
|
|
|
Hydrotest (200 psi @ 2hrs.) of dry pipe system protecting parking garage level. PASSED
|