INSP-Final Inspection | 12/3/2014 | 12/3/2014 | 12/3/2014 | P | PASS |
Forrest France
|
|
|
Verified C/N items, as-built plans accepted. Points map and record of completion documents to be provided as agreed.
|
INSP-Alarm Testing | 12/1/2014 | 12/2/2014 | 12/2/2014 | A | PART |
Forrest France
|
|
|
Functional testing and inspection of the new fire alarm system completed. Items needed prior to final include as-built drawings reflecting field modifications to show four added strobes, deleted kitchen hood monitor, revised cd settings at the multi-purpose rooms and west corridor, riser points added for dry system pressure switches. Need to add notification at the kitchen area restroom. Post signage at the door to the FACP room.
|