INSP-Final Inspection | 11/10/2015 | 11/10/2015 | 11/10/2015 | P | PASS |
Jim Page
|
|
|
Final fire alarm passed/complete per activities entered by Tom Walsh on 29OCT2015.
|
INSP-Final Inspection | 10/29/2015 | 10/29/2015 | 10/29/2015 | P | PASS |
Thomas Walsh
|
|
|
Fire alarm system test of wings F & G, including all unit SDs. corridor SDs, manual pulls, notification devices (audibility), FSDs, elevator recall functions, etc. All tested OK. Two unit SDs had to be reprogrammed to activate correctly. NOTE: All fire sprinkler system testing completed with wing F &G.
|
INSP-Final Inspection | 10/21/2015 | 10/26/2015 | 10/26/2015 | A | PART |
Thomas Walsh
|
|
|
Fire alarm system test for parking garage #2, which is under wings EF&G.=, including manual pulls, elevator recall and shunt trip functions, and audio/visual notification devices - all tested OK
|