Permit Information
Permit NumberFIR14-00801
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 2396 N 14TH PL
Project NamePrescott Residence
Customer Number 
ePlanReviewYes
Description
The fire sprinkler scope of work consists of protecting a single level residence.

WUI Zone A, Class A Roof, Permit for the construction of a new 1,065 sq. ft., one story single family dwelling (1 bedroom, 1 bathroom, approximately 260 sq. ft. of covered patio/porch) with detached 336 sq. ft. detached garage with 376 sq. ft. attached shop and 393 sq. ft. of living space above (2 bonus rooms, 1 half bathroom).
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/19/20158/20/20158/20/2015APASS
DetailsJim Page
Final inspection passed/complete
INSP-Final Inspection6/11/20156/11/20156/11/2015PFAIL
DetailsJim Page
This is not a final inspection, this was an underground cover inspection (Pot Marked Inspection for proper cover depth) and an underground flush. Pipe is at an approved depth and supply line is flushed/complete
INSP-Conference6/10/20156/11/20156/11/2015ADONE
DetailsJim Page
Verfied with on site contact, "pot marks" are being provided to verify underground piping cover.
INSP-Final Inspection5/12/20155/18/20155/18/2015AFAIL
DetailsTroy Cobbley
No head located over riser in riser room.

Fire bell not located on street side of building, bell also needs sticker installed

No record of underground being approved for cover.

No record of underground flush witness.

No backflow preventer installed on fire riser.

CPVC riser mounted to far from wall.
INSP-Sprinkler Rough-in2/11/20152/11/20152/11/2015PPART
DetailsForrest France
Overhead work approved for cover, tenting and insulation install verified.
INSP-Sprinkler Rough-in2/3/20152/3/20152/3/2015PPART
DetailsForrest France
Verified stamped plans on site, completed overhead rough-in inspection. * NOTE: Need to verify tenting insulation prior to cover. No record to date of an UG fire supply line inspection prior to bury.
INSP-Sprinkler Rough-in1/30/20152/2/20152/2/2015ANR
DetailsForrest France
Missing approved plans on site. Need to verify cold cavity protection at riser transitions to upper ceiling levels.