INSP-Final Inspection | 1/9/2015 | 1/9/2015 | 1/9/2015 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 12/28/2014 | 12/29/2014 | 12/29/2014 | A | FAIL |
Troy Cobbley
|
|
|
See alarm testing inspection for today for list of correction items needed.
|
INSP-Alarm Testing | 12/28/2014 | 12/29/2014 | 12/29/2014 | A | DONE |
Troy Cobbley
|
|
|
Tested function of the horn/strobes. Need as-builts showing the adjustment of the candella's and the addition of the duct smoke detector. And then testing of the duct smoke detector. Need weather proof backbox for the strobe over the pool. "Water Bug" may not be listed for use with acid.
|