Permit Information
Permit NumberFIR14-00888
StatusFinaled
Name TRIBAL FIRE SYSTEMS
Site Address 1875 S CENTURY WAY
Project NameWings Addition
Customer Number 
ePlanReviewYes
Description
Install new NAC booster to accommodate new notification devices in the new section. Install water bug in the pool equipment room to detect liquid leaks. Associated with building permit BLD14-01208.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/9/20151/9/20151/9/2015PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection12/28/201412/29/201412/29/2014AFAIL
DetailsTroy Cobbley
See alarm testing inspection for today for list of correction items needed.
INSP-Alarm Testing12/28/201412/29/201412/29/2014ADONE
DetailsTroy Cobbley
Tested function of the horn/strobes. Need as-builts showing the adjustment of the candella's and the addition of the duct smoke detector. And then testing of the duct smoke detector. Need weather proof backbox for the strobe over the pool. "Water Bug" may not be listed for use with acid.