INSP-Final Inspection | 8/6/2015 | 8/6/2015 | 8/6/2015 | P | PASS |
Thomas Walsh
|
|
|
Final fire alarm system inspection. All system functions and operations tested OK. Could not put into service off-site due to many fire sprinklers still in trouble (valves closed) due to work that needed to be completed. All sprinkler systems are now in service and the FACP is cleared. System will remain in service from this point on. As Builts were recently submitted to the city for review with some minor changes in SFDs, etc.
|
INSP-Final Inspection | 8/4/2015 | 8/4/2015 | 8/4/2015 | P | PART |
Thomas Walsh
|
|
|
Completion of fire alarm system testing, including test os all HVAC shutdown SDS that were not operating last visit. Tested DP valves in PG, however one system (north side) did not operate correctly. Tested all notification devices in garage that were missing at last inspection. Fire alarm system testing completed, except for fire sprinklers that need to be completed and retested.
|
INSP-Final Inspection | 8/3/2015 | 8/3/2015 | 8/4/2015 | P | CANC |
Thomas Walsh
|
|
|
Canceled fire alarm testing for today - rescheduled for tomorrow (8/4).
|
INSP-Final Inspection | 7/30/2015 | 7/31/2015 | 7/31/2015 | A | PART |
Thomas Walsh
|
|
|
Continuation of fire alarm system testing, including a trip test of the 5 dry-pipe fire sprinkler systems (see FIR14-00815) for results of these tests. Tested Elevator recall and shunt trip functions, completed testing of SDs for FSDs (all floors) HVAC shutdown SDs, and various SDs for panel rooms door closurers, etc. All tested OK. The DDs used for HVAC shutdown should be changed to latching devices so that the system needs to be reset before the unit restarts. Some device locations (descriptions) need to be changed to better decribe location or their purpose to aid respenders on locating the device in alarm. These will be rested next visit.
|
INSP-Final Inspection | 7/29/2015 | 7/30/2015 | 7/30/2015 | P | PART |
Thomas Walsh
|
|
|
Initial fire alarm system testing, including all fire sprinkler interface for wet-pipe systems, SDs SFD, etc. Dry pipe systems not tested yet, including trip test of dry-pipe valves.
|