INSP-Final Inspection | 8/20/2015 | 8/21/2015 | 8/21/2015 | A | PASS |
Jim Page
|
|
|
Final fire alarm inspection passed/complete
|
INSP-Final Inspection | 8/12/2015 | 8/12/2015 | 8/12/2015 | P | FAIL |
Troy Cobbley
|
|
|
Was only able to test the tamper for fire pump #1 suction valve today due to foam dump. Overhead doors and duct smoke detector not ready
|
INSP-Alarm Testing | 8/10/2015 | 8/11/2015 | 8/11/2015 | A | DONE |
Troy Cobbley
|
|
|
Todays testing included all tamper switches except Fire Pump #1 intake (needs replaced) and all flow and pressure switches. The hose valve tampers/riser are labeled incorrectly. Also tested the fire pump interconnection to the FACP. Risers and fire pumps need labeling to match the FACP display. Need signal reports. Need plans resubmitted due to extensive changes which include using a 4009 NAC panel for releasing and a wireless dialer instead of phone lines and door mags that need releasing upon flow of water.
|