INSP-Final Inspection | 7/14/2015 | 7/15/2015 | 7/15/2015 | P | PASS |
Jim Page
|
|
|
Previously noted items corrected, document cabinet with associated documents at the fire panel, sign posted on door leading to fire panel, alarm inspection passed/complete.
|
INSP-Final Inspection | 4/27/2015 | 4/28/2015 | 4/28/2015 | P | PART |
Katie Marron
|
|
|
Functional testing of new Alarm panel and radio transmitter complete. Verified NETCON, duct SD shut down of HVAC, all tampers, flows, and power troubles accurately reported panel and central station. Need document box, signage on door to panel and map of initiating devices posted at FACP to complete.
|
INSP-Final Inspection | 3/20/2015 | 3/23/2015 | 3/23/2015 | P | FAIL |
Forrest France
|
|
|
HVAC units did not shut down upon activation of duct smoke detectors, need to verify necton rating on site per review note comments, noted duct SD are programed as an alarm signal.
|