Permit Information
Permit NumberFIR15-00054
StatusFinaled
Name CURTIS FIRE SPRINKLER SERVICE INC
Site Address 10500 W OVERLAND RD
Project NameAlbertsons 160 tenant finish
Customer Number 
ePlanReviewYes
Description
[Albertsons 160 Tenant Finish]
The fire sprinkler scope of work consists of adding, plugging and relocating sprinklers to accommodate new wall and ceiling configuration.

Contractor’s Note:
The building permit has not been issued at this time. The building department may determine that changes are required to the building plans in order to meet code. The changes may affect the sprinkler system. The sprinkler contractor will be obligated to make all necessary changes that may be required. Therefore, if the sprinkler contractor chooses to proceed without an issued building permit, they will do so on their own cognizance. This note does not constitute an early start agreement.

Permit for tenant improvement of an existing 46,017 sq. ft. Albertsons store. Work to include the reconfiguration of the existing deli and bakery areas; relocation of an accessible restroom; removal cantilevered mezzanine; reconfiguration of check stands; installation of a new type one exhaust hood assembly and related interior finishes per the approved plans. A separate commercial cooking hood permit will be required for the necessary modifications to the hood suppression system. This building is fully fire sprinklered, any alterations to the sprinkler system will require a separate permit and shall comply with NFPA 13 as regulated by the fire department. CDM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/11/20155/11/20155/11/2015PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection4/2/20154/2/20154/2/2015PPASS
DetailsTroy Cobbley
Work is not yet complete at the south/east main exit (pendant head is overspaced)
INSP-Sprinkler Rough-in3/25/20153/26/20153/26/2015PPASS
DetailsTroy Cobbley
Piping ok to cover at the Bakery soffits
INSP-Sprinkler Rough-in2/25/20152/26/20152/26/2015APART
DetailsTroy Cobbley
Piping is soffit is ok to cover, pendant heads will be required above small coolers as discussed
INSP-Sprinkler Rough-in2/25/20152/25/20152/25/2015PCANC
DetailsTroy Cobbley
Overbooked
INSP-Sprinkler Rough-in2/13/20152/17/20152/17/2015APASS
DetailsTroy Cobbley
Partial ok to cover in Deli Area