Permit Information
Permit NumberFIR15-00064
StatusFinaled
Name WEBSTER FIRE PROTECTION
Site Address 1150 N CURTIS RD
Project NameBureau of Reclamation
Customer Number 
ePlanReviewYes
Description
Remodel of existing building. Replace existing Simplex fire alarm panel and replace with a new Silent Knight fire alarm panel. Monitoring of an existing Halon system. Elevator recall with shunt, sprinkler monitoring and full coverage notification are provided. Associated with building permit BLD14-03545. Plan modification received 5-29-15.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/23/20159/24/20159/24/2015APASS
DetailsTroy Cobbley
Permit finaled
INSP-Alarm Testing6/15/20156/16/20156/16/2015ADONE
DetailsTroy Cobbley
Todays inspection was for the hvac shut down of the units on the second floor.
INSP-Alarm Testing6/9/20156/10/20156/10/2015PDONE
DetailsTroy Cobbley
Todays testing was for the hvac shut down on the first floor only. See the city approved plans for locations marked ok. Will need to test the detector over the security desk and the dampers/separation between floors when installed.
INSP-Sprinkler Rough-in6/1/20156/2/20156/2/2015APART
DetailsTroy Cobbley
This inspection should have been scheduled as a final. A temporary occupancy is being given until the hvac shutdown, door mags and 3rd floor is complete.
INSP-Alarm Testing5/29/20156/1/20156/1/2015ADONE
DetailsTroy Cobbley
Water flow pressure switch has been corrected. Low air needs to be re-programmed. Need two door mag locks addressed as discussed. Tamper switches have been adjusted.
INSP-Alarm Testing5/26/20155/27/20155/27/2015PDONE
DetailsTroy Cobbley
Todays inspection we verified the Faast detection system (problems with low air and water flow), and verified the devices in the Warehouse. I noted that door mags are being used for security and will need to be addressed with the appropriate Fire Code and NFPA requirements.
INSP-Final Inspection5/22/20155/27/20155/27/2015ACANC
DetailsTroy Cobbley
Duplicate inspection
INSP-Final Inspection5/22/20155/26/20155/26/2015AFAIL
DetailsTroy Cobbley
Fire alarm testing for the first and second floors is complete. Correction previously noted have been address. Need HVAC issues addressed on all floors and the third floor fire alarm work completed.
INSP-Final Inspection5/22/20155/22/20155/22/2015PFAIL
DetailsTroy Cobbley
First floor corrections complete, second floor audio/visuals passed. Still need outside alarm bell repaired and heat detectors in elevator shafts tested. HVAC still needs to be addressed
INSP-Alarm Testing5/20/20155/21/20155/21/2015ADONE
DetailsTroy Cobbley
See the city approved plans for locations and devices tested which included the elevator recall. Elevator fire doors need to be adjusted/repaired, PIV needs adjusted and the outside alarm bell did not function.
INSP-Alarm Testing5/19/20155/20/20155/20/2015ACANC
DetailsTroy Cobbley
Ken and I agreed to reshedule for tomorrow morning at 7:00am
INSP-Alarm Testing5/18/20155/19/20155/19/2015ADONE
DetailsTroy Cobbley
Todays inspection verified the FACP and the NAC panel. Also verified tamper switches as marked on the city approved plans. Also verifed placement and function of the first floor NAC circuits/devices. I noted several overspaced strobes as marked on the plans. I spoke to the general contractor about duct smoke detectors (he is waiting on an RFI)