Permit Information
Permit NumberFIR15-00125
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 404 S 8TH ST
Project Name8th Street Market Remodel
Customer Number 
ePlanReviewYes
Description
[8th Street Market Remodel]-Quick Permit
Relocate 2 existing main line to accommodate the stairway modification. Add 2 new upright sprinklers to accommodate the new wall

There does not seem to be a building permit at this time.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/29/20154/30/20154/29/2015APASS
DetailsKatie Marron
Inspection completed on 4/29/15. Scope of work complete. Verified all heads are now standard response 200 degree. Permit finaled.
INSP-Final Inspection4/20/20154/21/20154/21/2015ACANC
DetailsKatie Marron
Robert is your contact on site. Please call 1/2 hour prior to inspection. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
INSP-Final Inspection4/20/20154/22/20154/21/2015PCANC
DetailsTroy Cobbley
Robert is your contact on site. Please call 1/2 hour prior to inspection. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
INSP-Sprinkler Rough-in4/17/20154/20/20154/20/2015PFAIL
DetailsKatie Marron
Mixed response heads; new are quick, existing are standard. Replace so heads match response and temperature.
INSP-Sprinkler Rough-in3/16/20153/17/20153/17/2015AFAIL
DetailsForrest France
Items noted include; mixed temp heads, plans indicate 200 deg. heads to be installed, overspaced coverage, field work completed exceeds scope of permit work shown on approved plans- additional heads have been added, coverage below stairs provided and a new riser manifold with control valves added. Need to resubmit plans matching work completed.