Permit Information
Permit NumberFIR15-00150
StatusFinaled
Name OMNI SECURITY SYSTEMS INC
Site Address 1777 S CURTIS RD
Project NameHeritage Assisted Living
Customer Number 
ePlanReviewNo
Description
Add notification to an existing fire alarm system. This project is not associated with a building permit. Plan modification 4-9-15 to correct deficiencies found during 1st inspection. Plan modification 5-18-15 for removal of detectors from Garden Room.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/27/20155/28/20155/29/2015APASS
DetailsTroy Cobbley
Permit finaled
INSP-Alarm Testing5/5/20155/12/20155/12/2015AFAIL
DetailsTroy Cobbley
Horn/strobe has been added to Laundry Room, smoke detectors have not been added to the Garden Room, knox box installed, map installed, set off notification and found that sync'ing is an issue with the sound and possibly with the strobes. I stopped the inspection of the horn/strobes as not to continue dicomfort of the tenants.
INSP-Alarm Testing4/13/20154/16/20154/16/2015ACANC
DetailsTroy Cobbley
Called contacts phone at 9:00am and left message for working out an inspection time. Stopped at project at 9:45 to see is contact was on site but found no one. I let Scott know. I later received phone call stating that the number is a wrong number. Eric Phone #: ###-####
INSP-Alarm Testing4/13/20154/15/20154/16/2015PDONE
DetailsTroy Cobbley
Todays inspection consisted of verifying that the panel model, NAC model, phone lines, batteries, wire guage at the FACP, revised horn/strobe layout and initial smoke detector layout was correct. Noted corrections are missing smoke detectors in the Garden Room, need strobe coverage in Laundry Room in Memory Care and possible strobe coverage in the east corridor area just outside of Memory Care. Also no sprinkler devices were checked. Missing Knox box and map at the FACP. Need to verify all requirements in the review comments and the revised drawings have been met.
INSP-Final Inspection4/1/20154/2/20154/2/2015PCANC
DetailsTroy Cobbley
Overbooked. Will need to be rescheduled. I let Eric know.
INSP-Alarm Testing3/23/20153/26/20153/26/2015PFAIL
DetailsTroy Cobbley
Plans need to be re-submitted showing the additional notification devices needed and relocated NAC panels and NAC panel triggers. Several strobes are overspaced. Alot of old devices have not been removed. Strobes need to be added in common restrooms and Linen Rooms/Laundery Rooms. There are ceiling obstructions that effect strobe placement and smoke detector placement.