Permit Information
Permit NumberFIR15-00153
StatusFinaled
Name PROTEX
Site Address 3100 S VISTA AVE Unit: 200
Project NameI.C.R.M.P. 2nd Floor Remodel
Customer Number 
ePlanReviewYes
Description
Modification of the building's existing fire alarm system to incorporate new non-profit governmental organizations as tenants on the 2nd floor. Plan modification submitted 6-16-15. Owner has decided to replace the existing fire alarm panel. Plan modification received 8-28-15 to change some wall strobes ceiling and changes to sprinkler and elevator monitoring. Associated with building permit BLD14-03099.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/2/20159/3/20159/3/2015APASS
DetailsJim Page
Final fire alarm inspection passed/complete
INSP-Final Inspection8/26/20158/26/20158/26/2015PFAIL
DetailsTroy Cobbley
The only items test today was verifying the facp and nac panels, phone lines, elevator recall and fire sprinkler flow and tamper switches. I noted that the elevator power needs to be monitored but hat functions can remain as-is, all of the wall mount strobes are mounted too low, many of the strobes are overspaced, additional notification devices are required on the third floor in the areas that are to remain occupied. As-builts with these corrections and corrected floor plan layout will be required. I did not inspect any of the first floor or basement today.