INSP-Final Inspection | 9/2/2015 | 9/3/2015 | 9/3/2015 | A | PASS |
Jim Page
|
|
|
Final fire alarm inspection passed/complete
|
INSP-Final Inspection | 8/26/2015 | 8/26/2015 | 8/26/2015 | P | FAIL |
Troy Cobbley
|
|
|
The only items test today was verifying the facp and nac panels, phone lines, elevator recall and fire sprinkler flow and tamper switches. I noted that the elevator power needs to be monitored but hat functions can remain as-is, all of the wall mount strobes are mounted too low, many of the strobes are overspaced, additional notification devices are required on the third floor in the areas that are to remain occupied. As-builts with these corrections and corrected floor plan layout will be required. I did not inspect any of the first floor or basement today.
|