Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberFIR15-00177
StatusFinaled
Name ABSOLUTE FIRE PROTECTION
Site Address 2260 S COLE RD
Project NameS. Cole Building C
Customer Number 
ePlanReviewYes
Description
[South Cole Building C]
The fire sprinkler scope of work consists of protecting a new warehouse with a center rail gridded system. The 8” underground service is apparently existing. The system will be supplied by a 6” riser and backflow preventer. The building is being designed using the spec warehouse provision of the Boise Municipal Code.

To construct a new 25,165 square foot, one story commercial shell building.. This building will be constructed of concrete tilt-up exterior walls, steel interior structural columns and beams with metal roof deck. This permit also includes related site improvements. This is a shell permit only and no occupancy is allowed under this permit. Separate tenant improvement permits will be required to finish this building for occupancy. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/5/201510/6/201510/6/2015APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection10/5/201510/5/201510/5/2015PFAIL
DetailsTroy Cobbley
Tried to retest the electric alarm bell and found the the backflow preventor appears to be "cycling" and not allowing the flow switch to activate.
INSP-Final Inspection10/1/201510/5/201510/5/2015PFAIL
DetailsTroy Cobbley
Need test papers and tags for riser, bell did not work. Forward flush passed.
INSP-Final Inspection9/30/20159/30/20159/30/2015PCANC
DetailsTroy Cobbley
Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
INSP-Sprinkler Rough-in8/31/20159/1/20159/1/2015APASS
DetailsTroy Cobbley
Rough-in passed. Lay-in tile can be installed at pendants.
INSP-Sprinkler Rough-in/Hydro7/15/20157/15/20157/15/2015PPASS
DetailsJim Page
Overhead sprinkler piping hydrostatic test passed/complete
INSP-Sprinkler Rough-in/Hydro7/14/20157/15/20157/15/2015APASS
DetailsJim Page
Rough-in inspection passed/complete, still needs hydrostatic test on overhead piping
INSP-Supply line flush6/25/20156/26/20156/26/2015ADONE
DetailsJim Page
Supply line flush complete
INSP-Sprinkler Rough-in/Hydro5/12/20155/13/20155/13/2015APASS
DetailsKatie Marron
Underground hydro pass. System did loose 5 psig over 2 hours which is in the allowable ranger per code.
INSP-Sprinkler Rough-in/Hydro4/2/20154/2/20154/2/2015PPASS
DetailsTroy Cobbley
Underground rough-in passed. Piping can be covered
INSP-Sprinkler Rough-in4/1/20154/2/20154/2/2015ACANC
DetailsTroy Cobbley
Duplicate inspection
INSP-Sprinkler Rough-in4/1/20154/1/20154/2/2015PCANC
DetailsTroy Cobbley
Requested for wrong date