Permit NumberFIR15-00254
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 12336 W OVERLAND RD
Project NameDamsel in Defense
Customer Number 
ePlanReviewYes
Description
New Fire Sprinkler monitor system in new TI space. Associated with building permit BLD15-00353.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/5/20158/6/20158/6/2015PCANC
DetailsTroy Cobbley
Phone #: 2088705073 >> Inspection requested via mobile web by John Siewert Inspection cancelled from web by: Chris Siewert
INSP-Final Inspection5/20/20155/21/20155/22/2015PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection5/18/20155/19/20155/19/2015PFAIL
DetailsTroy Cobbley
1. Monitoring service not set up correctly.
2. All devices will need to be retested.
3. Need to provide knox box.
4. Provide document cabinet.
INSP-Final Inspection5/13/20155/14/20155/14/2015AFAIL
DetailsTroy Cobbley
No testing performed. Duct smoke detectors are not wired up or tested, smoke detector at the FACP is mounted too far from the deck, the tamper switch fot the PIV is not installed. I have not looked at the approved drawings yet.