Permit Information
Permit NumberFIR15-00301
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 5500 S FEDERAL WAY
Project NameORPAC FA Replacement
Customer Number 
ePlanReviewYes
Description
ORPAC warehouse expansion job is to add a FA sprinkler monitoring system. New Simplex FACP 4007 panel to monitor fire sprinkler riser and a new fire pump. Associated with building permit BLD14-01628.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/19/20158/19/20158/19/2015PPASS
DetailsJim Page
Previously noted items corrected, final alarm inspection passed/complete
INSP-Final Inspection8/18/20158/18/20158/18/2015PPART
DetailsJim Page
Previously noted items not corrected, still need label on door for FACP Room, no document cabinet at FACP and no floor plan with initiating devices posted at FACP
INSP-Final Inspection5/5/20155/6/20155/6/2015PPART
DetailsKatie Marron
Partial final pass. Functional alarm test complete with the exception of flow switches on risers 1 & 2. Prior to final the following items to be completed: provide updated plans, provide knox box, provide document box, "Fire Alarm Control Panel" signage on doors, floor plan with initiating devices posted at FACP, and repaint alarm bell and add call 911 when sounding verbage.
INSP-Sprinkler Rough-in/Hydro5/5/20155/6/20155/5/2015PCANC
DetailsTroy Cobbley
Call prior to going Phone #: 2089414511 >> Inspection requested via mobile web by Nathan Price Inspection cancelled via mobile web on Tuesday, May 05, 2015.