Permit Number | FIR15-00307 |
Status | Finaled |
Name |
ABSOLUTE FIRE PROTECTION
|
Site Address |
646 N FIVE MILE RD
|
Project Name | Cradle Point Expansion - Racks |
Customer Number | |
ePlanReview | Yes |
Description |
[Cradle Point Expansion - Racks]
The fire sprinkler scope of work consists of adding new racks storing group A plastics at 18’ high. A new rack riser is being added.
CRADLE POINT) For tenant improvements to expand the existing Cradle Point space from 19,623 sq. ft. to 29,553 sq. ft. The additional space is S-1 storage space to have racking installed under a separate permit. This building is fully fire sprinklered for area. Any alterations to the sprinkler system will require a separate permit and shall comply with NFPA 13 as regulated by the fire department. CDM
Location on Plan - Racks
Commodity - Plastic Routers
Classification - Group A
Storage Type (rack, solid pile, etc.) - Double and Single Row Racks
Pallet Type (wood or plastic) - Wood
Aisle Width - 8’
Height of Storage - 18’
Ceiling Height - 23’
Encapsulated - No
Solid Shelves - No
Smoke and Heat Vents - No
Draft Curtain - No
In Rack Sprinklers - Yes
Sprinkler Type - 8.0 K
High Temperature Sprinklers Required - No
Applicable NFPA Section - Fig 17.2.1.2.1(d) Bot Right
Hydraulic Design Criterion - .30/2000 + (8) Sprk @ 15#
Hose Stream Requirements - 500
|