Permit Information
Permit NumberFIR15-00316
StatusFinaled
Name WEBSTER FIRE PROTECTION
Site Address 1150 N CURTIS RD
Project NameBureau of Reclamation
Customer Number 
ePlanReviewYes
Description
Installation of an early warning air sampling smoke detection system in computer room for pre-action system activation and sprinkler monitoring with full notification of a seperate warehouse building. Associated with building permit BLD14-03545 and existing fire alarm permit FIR15-00064.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/25/20159/25/20159/25/2015PPASS
DetailsTroy Cobbley
permit finaled
INSP-Alarm Testing6/1/20156/2/20156/2/2015APART
DetailsTroy Cobbley
A temporary is being given until the door mag in the warehouse has been addressed.
INSP-Alarm Testing5/29/20156/1/20156/1/2015ADONE
DetailsTroy Cobbley
The water flow pressure switch now functions. Still need the low air switch re-programmed the door mags and lightning protection in the warehouse addressed.
INSP-Alarm Testing5/26/20155/27/20155/27/2015PFAIL
DetailsTroy Cobbley
The low air signal needs to be a "supervisory" signal, not an alarm signal. The "waterflow" pressure switch on the pre-action system did not activate upon the trip of the system.