Permit Information
Permit NumberFIR15-00329
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 777 W MAIN ST
Project NameCity Center Plaza UG Stub-ins
Customer NumberUDG ONLY
ePlanReviewYes
Description
[City Center Plaza Underground] - Quick Permit
Shilo will connect in 3 locations at the property line where United Water has installed new 8" C900 pipe and install 8 X 6 reducer, 6" Yard PIV, and 6" C900 into the building (approximately 5'-0).

Plan Mod #1 - 8/01/2016
Remove the yard PIV and use a 2-hour rated riser room.

(CITY CENTER PLAZA) - Shell and Core Only - To complete the shell, core and exterior finishes for the 299,750 square foot, nine story office, retail, parking garage and convention center building with a 44,050 square foot, below grade bus transit center. This building is considered an addition to the existing approximate 304,610 square foot US Bank high rise building for allowable area, exterior opening and wall requirements. The existing high rise and new high rise addition will have separate sprinkler and alarm systems, as well as, their own fire command centers. This is a shell and core permit only and no occupancy is allowed under this permit. Separate tenant improvement permits will be required to finish this building for occupancy. All construction per the approved plans and attached comment list. JCM ***HIGH PRIORITY REVIEW***Contact Angie Brosious with any issues.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/4/20168/4/20168/4/2016APASS
DetailsJim Page
Final underground inspection passed/complete
INSP-Supply line flush8/3/20168/4/20168/4/2016ADONE
DetailsJim Page
North main line flush completed after PIV relocation.
INSP-Final Inspection8/1/20168/1/20168/1/2016PPASS
DetailsJim Page
Final underground fire sprinkler supply main inspection complete.
INSP-Sprinkler Rough-in/Hydro6/27/20166/29/20166/29/2016APART
DetailsJim Page
Hydrostatic test for south side underground supply complete.
INSP-Supply line flush6/27/20166/29/20166/29/2016ADONE
DetailsJim Page
South side underground supply main flushed
INSP-Supply line flush5/4/20165/6/20165/6/2016APASS
DetailsJim Page
Underfround flush for underground supply piping complete for both underground supplies.
INSP-Sprinkler Rough-in/Hydro5/4/20165/4/20165/4/2016PPASS
DetailsJim Page
200 psi hydrostatic test for underground supply piping passed/complete.
INSP-Sprinkler Rough-in4/22/20164/22/20164/22/2016PPASS
DetailsJim Page
North post indicator valve relocated to line up with landscaping, Rough to cover inspection for relocation/thrust blocks complete, approved for cover.
INSP-Sprinkler Rough-in4/21/20164/21/20164/21/2016APART
DetailsJim Page
South supply main post indicator valve relocated to line up with tree location, underground inspection for relocation passed/complete. Relocation for north post indicator will be completed at later date.
INSP-Sprinkler Rough-in10/29/201510/29/201510/29/2015PPART
DetailsThomas Walsh
Rough to cover inspection for fire service underground supply line (south side) for the convention center fire sprinkler systems. A portion of the supply line was sleeved as it passed through a foundation wall.
NOTE: Supply line changed from permit set of plans, showing a change in layout - thrust blocks added for these changes as required. OK to cover pipe.
NOTE: Contractor accepts the risk of burying pipe prior to hydrostatic test.
INSP-Supply line flush10/27/201510/28/201510/28/2015AFAIL
DetailsThomas Walsh
Rough inspection of fire service underground supply line (south side) into convention center portion of the building. U/G supply line penetrates building foundation without proper clearanace. Contractor agreed to remove pipe as needed to provide a clearance sleeve (10") around the 6" supply line.
INSP-Sprinkler Rough-in6/3/20156/3/20156/3/2015PPART
DetailsJim Page
Two of the three stub-ins are ready for inspection. The two inspected at this time are the two stub-ins on the west side of the building, both west side stub-ins are approved for cover. The third stub-in still needs to be installed/ inspected before cover can be accomplished..
INSP-Sprinkler Rough-in/Hydro6/1/20156/2/20156/3/2015PCANC
DetailsJim Page
Spoke to the onsite point of contact for this inspection, Bryan Phone #: ###-####, the underground was not ready for inspection, verbally confirmed over the phone for inspection cancellation.