Permit Information
Permit NumberFIR15-00574
StatusFinaled
Name PROTEX
Site Address 1173 W UNIVERSITY DR
Project NameBSU Alumni and Friends Center
Customer Number 
ePlanReviewYes
Description
Provide a code compliant fire alarm system to a 4 story building with event spaces on the 1st floor and offices on floors 2-4. System includes full detection and notification, duct detection, sprinkler monitoring, elevator recall and shunt. Associated with building permit BLD14-02741.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/30/201610/3/201610/3/2016APASS
DetailsJim Page
Final fire alarm inspection passed/complete.
INSP-Final Inspection9/29/20169/30/20169/30/2016APART
DetailsJim Page
Partial final complete for alarm system. Audio visual devices and photo smoke detectors tested on every floor, AHU shutdown tested for rooftop untis. Tamper switches needed to be added to the fire pump isolation valve as well as backflow, tamoers were installed at time of inspection but will ned to be wired up. Wood beam in ballroom was blocking flash from the ceiling mounted strobe, two additional strobes will be mounted and tested during next inspection.