Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberFIR15-00618
StatusFinaled
Name TRIBAL FIRE SYSTEMS
Site Address 12301 W EXPLORER DR
Project NameSyringa Networks Fire Alarm
Customer Number 
ePlanReviewYes
Description
Replace existing fire panel with a non-proprietary Silent Knight panel. Replace all existing addressable devices, the existing NAC devices and NAC booster are to be removed. They are not required by code. This permit also includes monitoring of two new duct detectors and the new clean agent suppression system in the current Syrings Networks C0-Locate T.I. This permit does not include the future T.I.'s for the vacant spaces or other future T.I.'s for Syringa Networks. This permit is only to replace the existing fire panel and addressable devices. This work is not associated with a building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/29/20163/1/20163/1/2016APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection2/23/20162/24/20162/24/2016PFAIL
DetailsTroy Cobbley
Will be ok to final when the SImplex permit for the dialer is finaled.
INSP-Final Inspection1/31/20162/1/20162/1/2016PFAIL
DetailsTroy Cobbley
See the city approved drawings for list of correctins needed for a final
INSP-Final Inspection1/28/20161/29/20161/28/2016PCANC
DetailsTroy Cobbley
Have appointment in the morning, free after 10:00 all day. Phone #: ###-#### >> Inspection requested via web by Brian Richard Inspection cancelled from web by: Brian Richard
INSP-Final Inspection1/26/20161/27/20161/28/2016PCANC
DetailsTroy Cobbley
Phone #: ###-#### Inspection requested via web by Brian Richard
INSP-Final Inspection1/25/20161/26/20161/26/2016PCANC
DetailsTroy Cobbley
Phone #: ###-#### >> Inspection requested via web by Brian Richard Inspection cancelled from web by: Brian Richard
INSP-Alarm Testing12/17/201512/24/201512/24/2015ADONE
DetailsJim Page
Notated devices tested on city approved drawings.
INSP-Alarm Testing12/17/201512/23/201512/23/2015ADONE
DetailsJim Page
Notated devices tested/passed on city approved drawings.
INSP-Alarm Testing12/18/201512/22/201512/22/2015PDONE
DetailsTroy Cobbley
See the city approved plans for corridor detectors tested today. The fire doors did not release upon alarm of the corridor detectors, water flow switch did not function, elevator hat did not function. We tried to test some duct smoke detectors but the units would not turn on.
INSP-Alarm Testing12/14/201512/21/201512/21/2015PDONE
DetailsTroy Cobbley
As-builts are needed showing deleted devices, added devices and address changes. Verified battery size in panel and panel model. Verifed a/v's have been removed per the approved plans. I noted that the smoke detectors for door release will need to be centered on doors. The access controled egress doors will need to be connected to the fire alarm system per the IFC. Interior doors on hold opens need to release on alarm and when the panel becomes inactive as discussed.
INSP-Alarm Testing12/17/201512/22/201512/18/2015ACANC
DetailsTroy Cobbley
>> Inspection requested via web by Brian Richard Inspection cancelled from web by: Brian Richard
INSP-Alarm Testing12/14/201512/16/201512/14/2015PCANC
DetailsTroy Cobbley
Phone #: ###-#### >> Inspection requested via web by Brian Richard Inspection cancelled from web by: Brian Richard
INSP-Alarm Testing12/14/201512/17/201512/14/2015PCANC
DetailsTroy Cobbley
Phone #: ###-#### >> Inspection requested via web by Brian Richard Inspection cancelled from web by: Brian Richard
INSP-Alarm Testing12/14/201512/18/201512/14/2015ACANC
DetailsTroy Cobbley
following and during clean agent inspection FIR15-00513 Phone #: ###-#### >> Inspection requested via web by Brian Richard Inspection cancelled from web by: Brian Richard
INSP-Sprinkler Rough-in/Hydro12/14/201512/18/201512/14/2015PCANC
DetailsTroy Cobbley
Phone #: ###-#### >> Inspection requested via web by Brian Richard Inspection cancelled from web by: Brian Richard