Permit Information
Permit NumberFIR15-00701
StatusFinaled
Name THORPE FIRE SPRINKLER SYSTEMS
Site Address 2284 E WALLING DR
Project NameFalling Brook Condos Bldg 3
Customer Number 
ePlanReviewYes
Description
[Falling Brook Condos Building #3]
The fire sprinkler scope of work consists of protection a 8 unit 2 level condominium. The protection is designed per NFPA13R. The systems utilizes CPVC piping and extended coverage residential sprinklers.

(FALLING BROOK CONDOS – Building #3) Permit is to construct an 8-unit 14,320 square foot residential apartment building with 7,234 sq. ft. on the first story and 7.086 sq. ft. on the second story. This building is to be constructed on an existing foundation and is separated into three building areas by two firewalls. This building is fully fire sprinklered for occupancy group R2. All work per the approved plans and the attached engineering. All of the units in this building are two story and are not required to be accessible. CDM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/13/20165/17/20165/17/2016PPASS
DetailsJim Page
Final fire sprinkler inspection passed/complete
INSP-Final Inspection5/12/20165/13/20165/13/2016APART
DetailsJim Page
Partial final inspection complete, inspection of apartments/garages passed/complete, will be able to be signed off as complete when fire alarm inspection has been performed, verification of signals from flow swith/tamper switches needs to be completed before permit can be finaled.
INSP-Supply line flush3/1/20163/3/20163/3/2016ADONE
DetailsJim Page
Underground main supply flush complete.
INSP-Sprinkler Rough-in1/7/20161/7/20161/7/2016PPASS
DetailsJim Page
Tenting inspection passed/complete, all piping for this building approved for cover.
INSP-Sprinkler Rough-in1/5/20161/5/20161/5/2016PCANC
DetailsJim Page
Spoke with Anthony, phone number ###-####, contractor will reschedule this inspection request to coincide with tenting for rough to cover. this inspection request cancelled per conversation with Anthony.
INSP-Sprinkler Rough-in1/4/20161/4/20161/4/2016PPART
DetailsJim Page
First floor rough to cover inspection passed/complete, approved for cover. 2nd floor piping still needs tenting installed, cannot cover 2nd floor piping until tenting is inspected and approved.
INSP-Sprinkler Rough-in/Hydro12/21/201512/22/201512/22/2015APASS
DetailsJim Page
200 psi hydrostatic test for 2 hours passed/complete for overhead fire sprinkler piping.
INSP-Sprinkler Rough-in/Hydro12/18/201512/21/201512/21/2015ACANC
DetailsJim Page
Hydrostatic test cancelled per coversation with POC, Anthony phone# ###-####, will be rescheduled for later date.
INSP-Sprinkler Rough-in/Hydro12/18/201512/18/201512/18/2015PFAIL
DetailsTroy Cobbley
Went back for a second time and was unable to verify test due to contractor draining system after finding a leak.
INSP-Sprinkler Rough-in/Hydro12/17/201512/17/201512/17/2015PFAIL
DetailsJim Page
Contractor had a dry fit, system could not hold 200 psi, contractor will reschedule hydrostatic test for overhead.
INSP-Sprinkler Rough-in/Hydro12/16/201512/17/201512/17/2015ACANC
DetailsJim Page
Please give Jake a call when you are headed out! Thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
INSP-Sprinkler Rough-in/Hydro12/14/201512/16/201512/16/2015ACANC
DetailsJim Page
Spoke with point of contact, Anthony, phone #: ###-####, project is not ready, he will reschedule inspection for a later date. Inspection request cancelled.