Permit NumberFIR15-00713
StatusFinaled
Name ABSOLUTE FIRE PROTECTION
Site Address 10722 W JEWELL LN
Project NameCordillera II, Bldg 3
Customer Number 
ePlanReviewYes
Description
[Cordillera II Building 3]
The fire sprinkler scope of work consists of CPVC piping is being used with extended coverage residential sprinklers to protect a two level, four unit apartment building using NFPA 13R

(CORDILLERA DEVELOPMENT PHASE 2 - BLDG 3) revisons to footing calculations and 310 form. **10/8/15 ajs** To construct a new 3,680 sq. ft., two story, Four unit, apartment building. Units 'A' have one bedroom, one den, and two bathrooms. Units 'B' have two bedrooms, and two bathrooms. All 4 dwelling units have their own independent exit. All construction per the approved plans, attached plan review report, and all other reviewing agencies approvals. One hour fire-partition separations are required between dwelling units. This building is required to be fire sprinklered. The fire sprinkler system shall be per NFPA 13R as regulated by the fire department. **AJS**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/15/20162/17/20162/17/2016APASS
DetailsTroy Cobbley
permit finaled
INSP-Supply line flush2/15/20162/16/20162/16/2016APASS
DetailsTroy Cobbley
Underground flush passed
INSP-Sprinkler Rough-in/Hydro2/11/20162/12/20162/12/2016AFAIL
DetailsTroy Cobbley
Started test but the fitter found a leak at a 90.
INSP-Sprinkler Rough-in/Hydro2/10/20162/11/20162/11/2016PPASS
DetailsTroy Cobbley
Overhead hydro test passed
INSP-Supply line flush2/10/20162/11/20162/11/2016ACANC
DetailsTroy Cobbley
Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
INSP-Sprinkler Rough-in12/3/201512/4/201512/4/2015APASS
DetailsTroy Cobbley
Rough-in and tenting passed and piping can be covered.
INSP-Sprinkler Rough-in11/25/201511/30/201511/30/2015APASS
DetailsTroy Cobbley
Underground supply is ok to cover
INSP-Sprinkler Rough-in10/27/201510/28/201510/28/2015AFAIL
DetailsTroy Cobbley
Pipe is not at the minimum 4'-6" bury