INSP-Final Inspection | 11/15/2016 | 11/15/2016 | 11/15/2016 | A | PASS |
Jim Page
|
|
|
Permit finaled
|
INSP-Final Inspection | 11/14/2016 | 11/14/2016 | 11/14/2016 | P | PASS |
Jim Page
|
|
|
Final Fire Alarm inspection complete
|
INSP-Final Inspection | 11/10/2016 | 11/10/2016 | 11/10/2016 | P | PASS |
Scott Arellano
|
|
|
Completed fire alarm inspeciton of commercial kitchen area and associated exit passageway. Completed testing and inspection of exterior passageway protection; per engineered fire alarm drawings withing electrical plan sheets under FIR16-00128.
|
INSP-Final Inspection | 9/16/2016 | 9/16/2016 | 9/16/2016 | P | PART |
Jim Page
|
|
|
Partial final fire alarm inspection for the district side of the convention center complete. Items still needing to be inspected is the kitchen area of level 1. Area labeled as level 5, level 4 , level 3 parking, level 2 parking, level 2 and level 1 lobby area complete for audio/visual notification on fire alarm system.
|
INSP-Final Inspection | 8/1/2016 | 8/1/2016 | 8/1/2016 | P | PART |
Jim Page
|
|
|
Partial final inspection complete for core and shell audio visual devices associated with this permit, A/V's on floors 1 through 9 associated with core and shell complete, door holders on floors 5, 6, 7, and 8 have been tested and work correctly, flow switches and tampers on the fire sprinklers floor 1 through 9 have been completed.
|
INSP-Sprinkler Rough-in/Hydro | 8/1/2016 | 8/1/2016 | 8/1/2016 | P | CANC |
Jim Page
|
|
|
Inspection request for alarm final, not for sprinklers, inspection request cancelled and a new inspection request will be generated.
|
INSP-Conference | 7/29/2016 | 8/1/2016 | 8/1/2016 | A | DONE |
Jim Page
|
|
|
Fire conference complete
|
INSP-Conference | 7/27/2016 | 7/28/2016 | 7/28/2016 | A | DONE |
Jim Page
|
|
|
Fire alarm conference complete, tested smoke detectors associated with shell and core on levels 1 through 9, tested audio visual devices associated with shell and core on floors 1 through 9, tested loss of battery power trouble at main panel.
|
INSP-Conference | 7/11/2016 | 7/12/2016 | 7/12/2016 | A | DONE |
Jim Page
|
|
|
Conference complete, tested flow switches and valve tamper switches for levels 1 throught 9 and wet pipe sprinkler systems, all tested satisfactorily.
|
INSP-Conference | 7/6/2016 | 7/8/2016 | 7/8/2016 | A | CANC |
Jim Page
|
|
|
Conference request cancelled per conversation with Ken, Phone #: ###-####.
|